• Cables •
• Cables •
FIRE-TECH Cable
FIRE-TRON Fire Detection
Fire Resistant Cable – PH30 / PH120
Application
Fire rated cables are designed to ensure circuit continuity in the event of a fire. Primarily intended for use in fire detection and fire alarm systems, emergency lighting circuits or if cables need to properly operate when fire resistance improvement is required. Suitable for indoor installation for platforms, pipe, conduits etc.
Cable available shielded with Aluminium/polyester and unshielded.
Fire rated cable conforms to IEC/EN 60332.3-24;
EN 60332-3-25
Flame retardant as per IEC/EN 60332.1-2
TEMPERATURES Operating: 0°C to 80°C Conductor Max: 180°C Short Circuit: 350°C | |
VOLTAGE RATING U U 300 500 V | |
MIN. BENDING RADIUS 10 x OD | |
LOW SMOKE EMISSION Transmittance > 60% (IEC 61034-2) |
Annealed copper conductors as per EN 60228 Class 5.
Core insulation ceramifiable silicone rubber.
Twisted pairs with polyester foil tape.
Annealed stranded tinned copper drain wire.
Shielded with aluminium/PET foil
Outer sheath thermoplastic halogen free compound (TI7) as per EN 50363-3; EN 50267-2-1.
Outer sheath colour Red (RAL 3000)
PH30:
120 minutes at 830°C in accordance with EN 50200
30 minutes at 950°C in accordance with BS 6387 cat. CWZ
PH120:
120 minutes at 950°C per BS 6387 cat. CWZ
Outer sheath Red or White. Additional colours on request. Alternatively, available
in mineral fibre (Mica) construction per EN50200
x = PH30 / PH120
Cable Print:
FIRE-TRON 2 x 1.00 100/100V PH30(/120) CEI 20-105 UNI 9795
CEI UNEL 36762 C-4 (U =400 V) EN 50200 CEI EN 60332-3-25
(Production Batch) CE (Meter marking)
Marking Colour:
Blue